CC7-1600B

CC-Link, Integrated I/O, 16DI, PNP

IP67 protection level, suitable for harsh industrial environments

Supports digital quantity input delay 1.5ms, filters out microsecond invalid signals

Using standard cable wiring is simple and the layout is quick

The configuration is simple, supporting mainstream CC-Link masters such as Mitsubishi

Compare

Interface Parameters

ProtocolCC-Link
Data Transfer MediumCC-Link dedicated cable (three-core shielded cable)
Data Transfer RatesFive speed rates can be set: 10 Mbps / 5 Mbps / 2.5 Mbps / 625 kbps / 156 kbps
Distance Between Stations≤100 m / ≤160 m / ≤400 m / ≤900 m / ≤1200 m
Electrical Isolation500V
Bus ConnectionIN:M12,4Pin ,A-code,PIN-end,blue
OUT:M12,5Pin,A-code,HOLE-end,blue

Technical Parameters

Power Supply24 VDC(18V~30V)
Weight480g
Module Size225×62×35.1mm
Protect. ClassIP67
Operating Temperature-25~+70℃
Storage Temperature-40~+85℃
Relative Humidity95%,no condensation
Power interface2×M12,5Pin,L-code,red
UStotal currentMax:16A
USpower consumption≤40mA
ULtotal currentMax:16A
ULpower consumption25mA + Sensor supply current + load output current
Electrical isolation between GNDS and GNDLYes

Digital Input

Nominal Voltage24 VDC(18V~30V)
Number of Inputs16
Transistor PolarityPNP
Input Current4 mA
Electrical Isolation500 VAC
IndicatorGreen LED
"0" Signal Voltage-3~+3 V
“1” Signal Voltage15~30 V
Input Interface8×M12,5Pin,A-code
Total Sensor Power SupplyMax:2A(from UL
Isolation MethodOptocoupler isolation
Input delay≤1.5 ms