EC7-0808B

EtherCAT, Integrated I/O, 8DI, 8DO, PNP, 0.5A (plastic housing)

IP67 protection level, suitable for harsh industrial environments

Based on high-performance EtherCAT ASIC communication chips, direct control, faster speed

Using standard cable wiring is simple and the layout is quick

The configuration is simple, supporting mainstream EtherCAT masters

Compare

Interface Parameters

Fieldbus Interface2 x M12, 4-pin, D-code, blue
Bus protocolEtherCAT
Data transmission mediumUTP or STP of Category 5 or higher (STP recommended)
Transmission distance<= 100 m (station-to-station distance)
Electrical Isolation500V

Technical Parameters

UL total currentMax:16A
UL current consumption25 mA + sensor supply current + load output current
Electrical isolation between GNDS and GNDLYes
Power Connector2 x M12, 5-pin, L-code, red
US total currentMax:16A
US current consumption≤35mA
Power Supply18~36VDC
Operating temperature-25 ~ +70℃
Protection ratingIP67
Dimensions225×62×35.1mm
Relative Humidity95 %, no condensation
Storage Temperature-40 ~ +85℃
Weight480g

Digital Input

Input Interface8×M12,5Pin,A-code
Total Sensor Power SupplyMax:2A(from UL)
Rated voltage24 VDC(±25%)
Number of Signal Points8
Signal TypePNP
Input Current4mA
Isolation withstand voltage500V
Channel indicatorGreen LED
"0" Signal Voltage-3~+3 V
"1" Signal Voltage15~30 V
Isolation methodOptocoupler Isolation

Digital Output

Output Interface8×M12,5Pin,A-code
Total output currentMax:4 A(from UL)
Rated voltage24 VDC(±25%)
Number of Signal Points8
Signal TypePNP
Load TypeResistive load, inductive load
Rated Current per ChannelMax:500 mA(from UL)
Port ProtectionOvercurrent protection
Isolation withstand voltage500V
Isolation methodOptocoupler Isolation