Supports three types of communication interfaces: RS485/RS422/RS232
Supports various communication modes such as Modbus RTU master-slave, Modbus ASCII master-slave, and Freeport
Configuration is simple and supports multiple bus protocols
Compact structure, small footprint
| Connection Method | Spring-loaded contact |
| Data transmission medium | X-bus backplane bus |
| Transmission rate | 6 Mb/s |
| Electrical Isolation | Yes |
| Number of channels | 1 channel |
| Communication interface type | RS232, RS485, RS422 |
| Communication Protocol | Modbus RTU, Modbus ASCII, Freeport |
| Baud Rate | 1200 bps ... 115200 bps |
| Power | 5 V DC (4.5 V ... 5.5 V) |
| Operating temperature | -20 °C ... +60 °C |
| Storage Temperature | -40 °C ... +80 °C |
| Weight | 90 g |
| Dimensions | 106.4 x 25.7 x 72.3 mm |
| Protection rating | IP20 |
| Relative Humidity | 95 %, non-condensing |
| Respond Timeout | 5 ... 3000 (default 50 ms) |
| Poll Delay | 5 ... 3000 (default 50 ms) |
| Slave Respond Delay | 0 ... 3000 (default 50 ms) |
| Communication Mode | 0: No selection 1: Modbus RTU master 2: Modbus RTU slave 3: Modbus ASCII master 4: Modbus ASCII slave 5: FP_Request (Free port Request mode) 6: FP_Input_Output (Free port input/output mode) 7: FP_Input (Free port input mode) 8: FP_Output (Free port output mode) |
| Serial port baud rate | 0: 1200 bps 1: 2400 bps 2: 4800 bps 3: 9600 bps 4: 19200 bps 5: 38400 bps 6: 57600 bps 7: 115200 bps |
| Stop Bit | 0: 1 bit 1: 2 bits |
| Parity | 0: No parity 1: Odd parity 2: Even parity |
| Word Format | 0: 8 bits 1: 7 bits |
| Modbus slave station number | .. 247 (valid in slave mode) |