Occupies fewer nodes, one coupler supports up to 32 slots and 1024 points
The filedbus coupler features four XBF expansion interfaces in RJ45 format, enabling daisy-chain connection of various types of I/O modules
The communication interface complies with communication standards, supporting mainstream EtherCAT master station
Featuring comprehensive indicator light design, module status is visible at a glance, thus simplifying inspection and maintenance
| Protocol | EtherCAT |
| Max. Number of IO Modules | Subject to the number of slave devices supported by the master station |
| Data Transfer Medium | Ethernet/EtherCAT CAT5 S/FTP cable |
| Data Transfer Rates | 100Mb/s |
| Distance Between Stations | ≤50m (total accumulated length from interface of the coupler to the last I/O module on this branch; each interface supports expansion with up to 16 modules) |
| Bus Connection | 2×RJ45 |
| Minimum Cycle Time | 250µs |
| Input and output process data volume | 1020Bytes |
| Expansion Module Interface | 4×RJ45 |
| The maximum cascade number of coupler slave station | 32 |
| The maximum number of cascaded slaves for a single interface | 16 |
| Coupler expansion interface data transmission medium | Ethernet/EtherCAT CAT5 S/FTP cable |
| The maximum transmission distance between discrete I/O modules | 30m |
| Weight | 140g |
| Module Size | 112.7×28×76mm |
| Protect. Class | IP20 |
| Operating Temperature | -20℃~+60℃ |
| Storage Temperature | -40℃~+80℃ |
| Relative Humidity | 95 %, no condensation |
| Input Voltage | SELV Input 24VDC(18V~36V) |
| Input Current | <0.95A |
| Module Abnormality Self-Recovery | Support |
| Access PDO through SDO | Support |
| Firmware Upgrade | Support |
| Power Supply Current | <500mA (max. supply current per interface); <750mA (combined maximum supply current for all four interfaces) |
| Power Supply Voltage | 20VDC~24VDC |
| Drop Line Check | Support |
| Short circuit protection | Support |
| Anti-reverse protection | Support |
| Surge protection | Support |