Supports selection of bridge voltage
Supports selection of bridge connection method
Each channel supports disconnection detection
Can set standard range, extended range two modes
| Protocol | X-bus |
| Data Transfer Rates | 6Mb/s |
| Connection Method | Reed Contact |
| Process data volume: Downlink | 4 Bytes |
| Process data volume: Upstream | 12 Bytes |
| Power Supply | 5 VDC |
| Weight | 120g |
| Module Size | 106×73×25.7 mm |
| Protect. Class | IP20 |
| Operating Temperature | -10℃~+60℃ |
| Storage Temperature | -20℃~+75℃ |
| Relative Humidity | 95%, no condensation |
| Disconnection detection | Support |
| Overflow function | Support |
| Input Filtering | Configurable |
| Channel indicator light | Green LED |
| Number of channel | 2 |
| Type of sensor | Full-bridge 4-wire/6-wire sensor, half-bridge 3-wire/5-wire sensor |
| Connection Method | Full bridge 4-wire system/6-wire system, half bridge 3-wire system/5-wire system. |
| Supply Bridge Voltage | 2V /2.5V /3V /3.5V /4V /4.5V /5V |
| Conversion speed | 5ms |
| Output speed | 1ms |
| Input range | Full bridge: ±32mV/V Half bridge: ±16mV/V |
| Range Mode | Standard range mode, extended range mode |
| Accuracy Requirements | 0.4‰ |
| Channel Disabled | Support |
| Channel Independent | Support |
| Zero point compensation | Half-bridge zero point compensation (16-bit compensation) |