Rich in measurement types, supports sensor type selection
Each channel supports disconnection detection
Sensitivity: 0.1℃, suppresses 50Hz AC power interference
Heating control self-tuning function, using a proprietary PID independent control algorithm
| Data transmission medium | X-bus backplane bus |
| Transmission rate | 6Mb/s |
| Rated current consumption | 80mA |
| Sensor wiring type | 2-wire, 3-wire |
| Sensor input temperature accuracy | ±0.5℃ |
| Sensitivity | 0.1℃ |
| Sensor Sampling Period | 4 channels 130 ms |
| Control accuracy | Max. overshoot 2 °C, ±0.5 °C at steady state |
| Control Cycle | 4 channels, 200 ms |
| Disconnection detection | Supported |
| Disconnection detection time | 2ms |
| Output signal | PWM output (Solid state Relay (SSR) trigger output) |
| Overflow/Underflow Function | Supported |
| Power Supply | Powered via the X-bus |
| Operating temperature | -10~60℃ |
| Relative Humidity | 95 %, non-condensing |
| Storage Temperature | -20~75℃ |
| Protection rating | IP20 |
| Dimensions | 106*73*25.7 mm |
| Weight | 120g |
| Sensor Type | RTD |
| Input Points | 4 |
| Resolution | 24 bit (int type) |
| Channel indicator | Green LED |