XB6S-A80TM-A

8-channel thermal resistance and thermocouple temperature acquisition module, supports external cold junction compensation and more sensor types.

Measurement types support thermocouples (TC), RTDs, and resistance (R)

Supports internal cold junction compensation, external cold junction compensation, and cold junction compensation disabled

Sensitivity: 0.1℃, supports single-channel filter settings

Temperature sensor supports disconnection detection

Compare

Interface Parameters

Data transmission mediumX-bus backplane bus
Bus connection methodSpring-Clamp contact
Transmission rate6Mb/s
Electrical IsolationYes

Technical Parameters

Power Supply5VDC(4.5V~5.5V)
Module Fault Auto-RecoverySupported
DiagnosticsSupported
alarmSupported
Firmware UpgradeSupported
Operating temperature-20℃~+60℃
Relative Humidity95 %, non-condensing
Storage Temperature-40℃~+80℃
Protection ratingIP20
Dimensions106.4*25.7*72.3mm
Weight110g

Analog

Input FilterSingle-channel Filtering, configurable (levels 1 to 10)
Power consumption0.55W
Sensor Typethermocouple, RTD, resistance
Conversion TimeThermocouple: 29 ms/ch, 115 ms/8 ch
RTD, resistance: 73 ms/ch, 290 ms/8 ch
Sensitivitythermocouple, RTD: 0.1 °C
Resistance: ±0.1 Ω
Noise Suppression50 Hz, 60 Hz, 10 Hz, no noise suppression
Excitation Current<2mA
Isolation withstand voltage500VDC
Input Points8
Signal Voltage/CurrentThermocouple: 29 ms/ch, 115 ms/8 ch
RTD, resistance: 73 ms/ch, 290 ms/8 ch
Resolution16 bit (int type)
AccuracyThermocouple: ±0.3 % @25 °C (F.S.), ±0.5 % @-20 ... 60 °C (F.S.)
RTD: ±0.1 % @25 °C (F.S.), ±0.3 % @-20 ... 55 °C (F.S.)
Resistance: ±0.1 % @25 °C (F.S.), ±0.3 % @-20 ... 55 °C (F.S.)
Input impedance≥10KΩ
Channel indicatorGreen LED