IP67 protection level, suitable for harsh industrial environments
Supports digital quantity input delay 1.5ms, filters out microsecond invalid signals
Using standard cable wiring is simple and the layout is quick
The configuration is simple, supporting mainstream CC-Link masters such as Mitsubishi
| Fieldbus Interface | IN: M12, 4-pin, A-code, male connector (pin), blue OUT: M12, 5-pin, A-code, female connector (socket), blue |
| Data transmission medium | CC-Link dedicated cable (3-Core Shielded cable) |
| Bus protocol | CC-Link |
| Transmission rate | Five speed settings are available: 10 Mbps / 5 Mbps / 2.5 Mbps / 625 kbps / 156 kbps |
| Transmission distance | ≤100 m / ≤160 m / ≤400 m / ≤900 m / ≤1200 m |
| Electrical Isolation | 500V |
| Power Connector | 2 x M12, 5-pin, L-code, red |
| US total current | Max:16A |
| US current consumption | ≤40mA |
| UL total current | Max:16A |
| UL current consumption | 25 mA + sensor supply current + load output current |
| Electrical isolation between GNDS and GNDL | Yes |
| Power Supply | 24 VDC(18V~30V) |
| Operating temperature | -25~+70℃ |
| Relative Humidity | 95 %, non-condensing |
| Storage Temperature | -40~+85℃ |
| Protection rating | IP67 |
| Dimensions | 225×62×35.1mm |
| Weight | 480g |
| Output Interface | 8×M12,5Pin,A-code |
| Total output current | Max:8 A(from U>sub>L) |
| Rated voltage | 24 VDC(18V~30V) |
| Number of Signal Points | 16 |
| Signal Type | NPN |
| Load Type | Resistive load, inductive load |
| Rated Current per Channel | Max:500 mA(from UL) |
| Port Protection | Overcurrent protection, Short-circuit Protection |
| Isolation withstand voltage | 500 VAC |
| Channel indicator | Green LED |
| Isolation method | Optocoupler Isolation |