MT4-A40V

Modbus TCP, Integrated I/O, U, 4 channels analog voltage input,-10~+10V / 0~+5V / 1~+5V, ±0.1% accuracy

Small in size, compact structure, only 102×72×25 mm

Built-in switch, dual hundred megabit industrial Ethernet port

Spring-loaded pluggable terminals for quick wiring

Simple configuration setup, can be cascaded, supports mainstream Modbus TCP masters

Compare

Interface Parameters

Number of I/O Stations127
Data transmission mediumEthernet CAT5 Cable
Bus connection method2*RJ45
Bus protocolModbus TCP
Transmission rate100Mb/s
Transmission distance<= 100 m (station-to-station distance)

Technical Parameters

Power Supply24VDC(18~36V)
Operating temperature0~+55℃
Relative Humidity95 %, non-condensing
Storage Temperature-20~75℃
Protection ratingIP20
Dimensions102*72*25mm
WeightApprox. 130 g
Power Connection Method3 Pin
Configuration methodvia master

Analog

Isolation withstand voltage500 V
Input Points4
Signal Voltage/Current-10~+10V (-32768~32767)
0~+10V (0~65535)
-10~+10 V (-27648~27648)
-5~+5 V (-27648~27648)
1~+5 V (0~27648)
2~+10 V (0~27648)
Resolution16 bit
Accuracy±0.1%
Input impedance≥2kΩ
Channel indicatorGreen LED
Signal TypeVoltage