PN7-0016A

PROFINET, Integrated I/O, 16DO, NPN, 0.5A (plastic housing)

IP67 protection level, suitable for harsh industrial environments

Based on high-performance communication chips, faster speed

Can switch between input and output functions by configuring DIO channel parameters

The configuration is simple, supporting mainstream PROFINET masters such as Siemens

Compare

Interface Parameters

Bus Connection2×M12,4Pin,D-code,blue
Data Transfer MediumCAT5e: UTP or STP(STP recommended)
ProtocolPROFINET
Distance Between Stations≤100m
Electrical Isolation500V

Technical Parameters

Power interface2×M12,5Pin,L-code,red
UStotal currentMax:16A
USpower consumption≤40mA
ULtotal currentMax:16A
ULpower consumption25mA + Sensor Supply Current + Load Output Current
Electrical isolation between GNDS and GNDLYES
Power Supply18~36 VDC
Operating Temperature-40~+85℃
Relative Humidity95 %, no condensation
Storage Temperature-20~75℃
Protect. Class-25~+70℃
Module Size225×62×35.1mm
Weight480g

Digital Output

Output Interface8×M12,5Pin,A-code
Output total currentMax:8 A(from UL)
Nominal Voltage24VDC(±25%)
Number of Outputs16
Transistor PolarityNPN
Load Typeohmic, inductive load
Max. Output CurrentMax: 500mA
Port ProtectionOvercurrent
Electrical Isolation500V
IndicatorGreen LED
Isolation MethodOptocoupler isolation