The measurement type supports TD, TC, RTD
Supports single-channel filter settings
Supports single-channel enable settings
All temperature sensors support disconnection detection
| Protocol | X-bus | 
| Max. Number of IO Modules | 32 | 
| Data Transfer Medium | X-Bus backplane bus | 
| Data Transfer Rates | 6Mb/s | 
| Power Supply | Power supply via X-Bus | 
| Current Consumption | 80mA | 
| Weight | 120g | 
| Module Size | 106*73*25.7 mm | 
| Protect. Class | IP20 | 
| Operating Temperature | -10~60℃ | 
| Storage Temperature | -20~75℃ | 
| Relative Humidity | 95 %, no condensation | 
| Analog Inputs | 8 | 
| Resolution | 16 bit | 
| Conversion Time | 201 ms (thermocouple) / 26 ms (RTD、resistor) | 
| Accurate | ±0.5% (thermocouple)/ ±1℃ (RTD) / ±0.1% (resistor) | 
| Electrical Isolation | 500Vrms, no isolation between channels | 
| Indicator | Green LED | 