XB6S-A40TM

4-channel thermal resistance and thermocouple temperature acquisition module

Measurement types support TC, TD, RTD

Sensitivity: 0.1℃, supports single-channel filter settings

Temperature sensor supports disconnection detection

Supports 50Hz, 60Hz, 10Hz, noise suppression configuration

Compare

Interface Parameters

Data transmission mediumX-bus backplane bus
Bus connection methodSpring-Clamp contact
Transmission rate6Mb/s
Electrical IsolationYes

Technical Parameters

Power Supply5VDC(4.5V~5.5V)
Module Fault Auto-RecoverySupported
DiagnosticsSupported
alarmSupported
Firmware UpgradeSupported
Operating temperature-20℃~+60℃
Relative Humidity95 %, non-condensing
Storage Temperature-40℃~+80℃
Protection ratingIP20
Dimensions106.4*25.7*72.3mm
Weight110g

Analog

Input FilterSingle-channel Filtering, configurable (levels 1 to 10)
Power consumption0.5W
Sensor Typethermocouple, RTD, resistance
Conversion TimeThermocouple: 29 ms/ch, 115 ms/8 ch
RTD, resistance: 73 ms/ch, 290 ms/8 ch
Sensitivitythermocouple, RTD: 0.1 °C
Resistance: ±0.1 Ω
Noise Suppression50 Hz, 60 Hz, 10 Hz, no noise suppression
Excitation Current<2mA
Isolation withstand voltage500VAC
Input Points4
Resolution16 bit (int type)
AccuracyThermocouple: ±0.3 % @25 °C (F.S.), ±0.5 % @-20 ... 60 °C (F.S.)
RTD: ±0.1 % @25 °C (F.S.), ±0.3 % @-20 ... 55 °C (F.S.)
Resistance: ±0.1 % @25 °C (F.S.), ±0.3 % @-20 ... 55 °C (F.S.)
Input impedance≥10KΩ
Channel indicatorGreen LED