Occupies fewer nodes, one coupler supports up to 32 slots and 1024 points
Supports flexible expansion and configuration, can integrate digital, analog, motion control modules etc.
The communication interface complies with communication standards, supporting mainstream Modbus TCP master station .
Uses X-bus backplane bus: minimum scan cycle is 200us, typical value is 1ms
| Minimum Cycle Time | 1ms |
| Input and output process data volume | 512Bytes |
| Protocol | Modbus TCP |
| Max. Number of IO Modules | 32 |
| Data Transfer Medium | Ethernet CAT5 cable |
| Bus Interface | 2*RJ45 |
| Data Transfer Rates | 100Mb/s |
| Distance Between Stations | 100m(station to station) |
| Module Abnormality Self-Recovery | Support |
| Alarm | Support |
| Firmware Upgrade | Support |
| Operating Temperature | -20~60℃ |
| Power Supply | 24VDC(18V~36V) |
| Relative Humidity | 95 %, no condensation |
| Storage Temperature | -40~80℃ |
| Protect. Class | IP20 |
| Module Size | 106.4*43*61mm |
| Weight | 160g |
| Power Interface | 3pin |