The MT4 series is an integrated I/O module with Modbus TCP protocol from Solidot, featuring dual industrial Ethernet ports, a Built-in Switch and a compact design. The series offers a complete range of module types, including digital and analog, and supports flexible configuration. For the configuration and operation issues commonly encountered by users in practice, this document provides concise guidance on key parameter settings and function applications.

1. Parameter configuration and IP address Change
First, locate the corresponding module as described in the wiring chapter of the MT4 Series integrated I/O user manual and wire it correctly according to the drawing. After powering on and connecting with an Ethernet cable from the PC, enter the module's default IP address 192.168.1.120 in the browser to access the configuration interface, as shown in the figure below:

The figure below shows the configurable parameters supported by the MT4 series. Among them—
"Disconnection Time" refers to the time after which the module determines it is offline when the master no longer sends messages. Setting it to 0 disables this function;
"Clear/Hold" refers to whether the outputs are cleared or held when communication between the module and the master is interrupted.
After changing the configuration parameters, click save and Restart below, and wait for the module to restart automatically for the changes to take effect.

2. Module Usage
1. Digital Usage
The digital function addresses are shown in the table below:
The module supports a total of 5 function codes: Read Coils 0 x 01 (1), Read discrete Inputs 0 x 02 (2), Write multiple Coils 0 x 0f (15), Read Holding Registers | ||||
Digital input/output address Mapping table | ||||
Read Coils 0 x 01 (1) | ||||
channel | Channel 0 | Channel 1 | … | Channel 127 |
start position | 0 | 1 | … | 127 |
Maximum Length | 128 | 127 | … | 1 |
Read discrete Inputs 0 x 02 (2) | ||||
channel | Channel 0 | Channel 1 | ... | Channel 63 |
start position | 0 | 1 | ... | 63 |
Maximum Length | 64 | 63 | ... | 1 |
Write multiple coils 0 x 0f (15) | ||||
channel | Channel 64 | Channel 65 | ... | Channel 127 |
start position | 64 | 65 | ... | 127 |
Maximum Length | 64 | 63 | … | 1 |
Read Holding Registers 0 x 03 (3) | ||||
channel | Channels 0 ... 15 | Channels 16 ... 31 | … | Channels 112 ... 127 |
Start Address | 0 | 1 | … | 7 |
Maximum Address | 8 | 7 | … | 1 |
Write multiple registers 0 x 10 (16) | ||||
channel | Channels 64 ... 79 | Channels 80 ... 95 | Channels 80 ... 111 | Channels 112 ... 127 |
Start Address | 4 | 5 | 6 | 7 |
Maximum Address | 4 | 3 | 2 | 1 |
The inputs can be read using function codes 01, 02 (bit read), 03 (word read), as shown in the figure below:

The outputs can be written using function codes 15 (bit write), 16 (word write), as shown in the figure below:

Note: only one function code may be used at a time for writing.
2. Analog Usage
(1) Reading and writing channels
The analog function addresses are shown in the table below:
Analog input/output address Mapping table | ||||||||
Read Holding Registers 0 x 03 (3) | ||||||||
channel | Channel 0 | Channel 1 | Channel 2 | Channel 3 | Channel 4 | Channel 5 | Channel 6 | Channel 7 |
Start Address | 8 | 9 | 10 | 11 | 12 | 13 | 14 | 15 |
Maximum Address | 8 | 7 | 6 | 5 | 4 | 3 | 2 | 1 |
Write multiple registers 0 x 10 (16) | ||||||||
channel | Channel 0 | Channel 1 | Channel 2 | Channel 3 | Channel 4 | Channel 5 | Channel 6 | Channel 7 |
Start Address | 16 | 17 | 18 | 19 | 20 | 21 | 22 | 23 |
Maximum Address | 8 | 7 | 6 | 5 | 4 | 3 | 2 | 1 |
The inputs can be read using function code 03, and the outputs can be written using function code 16, as shown in the figure below:

(2) Changing the analog range
To change the analog range, a value must be assigned to the address corresponding to each channel. The address for each channel is shown in the table below:
Analog range selection address correspondence table | ||||||||
Write multiple registers 0 x 10 (16) | ||||||||
8-channel analog range selection address correspondence table | ||||||||
channel | Channel 0 | Channel 1 | Channel 2 | Channel 3 | Channel 4 | Channel 5 | Channel 6 | Channel 7 |
Start Address | 32 | 33 | 34 | 35 | 36 | 37 | 38 | 39 |
Maximum Address | 8 | 7 | 6 | 5 | 4 | 3 | 2 | 1 |
Address correspondence table for analog range selection, 4-channel | ||||||||
channel | Channel 0 | Channel 1 | Channel 2 | Channel 3 | ||||
Start Address | 32 | 33 | 34 | 35 | ||||
Maximum Address | 4 | 3 | 2 | 1 | ||||
The measuring range can be changed as shown in the figure below. Since it is changed via a register, it must be written again after each power cycle of the module.
analog input | |
Input Points | 4, 8 |
Input signal (voltage type) | 0: -10 ... +10 V (-32768 ... 32767) |
Input signal (current type) | 0: 4 ... 20 mA (0 ... 65535) |
analog output | |
Number of Output Points | 4, 8 |
Output signal (voltage type) | 0: -10 ... +10 V (-32768 ... 32767) |
Output signal (current type) | 0: 4 ... 20 mA (0 ... 65535) |
Taking the MT4-A04V four-channel voltage output as an example:
Assign a code value of 20000 to the outputs at the same time
Measuring range of channel 1 is 0:
-10 V ... 10 V (-32767 ... 32767), output voltage is 6.11 V
Measuring range of channel 2 is 1:
.. 10 V (0 ... 65535), output voltage is 3.06 V
Configuration is successful once it is set up as shown in the figure below.

This concludes the Solidot Modbus TCP integrated module quick start guide. Thank you for watching.