Detailed Configuration of Digital Inputs on Solidot's XB6S PTO Module

The Solidot PTO pulse output module XB6S-PT04A can be connected to an external stepper/servo motor driver and drives the stepper/servo motor by outputting pulses. In some application scenarios, the digital input channels of the module need to be used as standard DI inputs during operation. This article provides a detailed explanation of the configuration method.

1. Input channel function configuration description

This module allows any digital input to be changed to standard mode, i.e. the Positive/Negative Limit, Home position and Brake functions are disabled. The 4 channels occupy a total of 16 bits; setting the corresponding bit to 1 configures it as a standard digital input.

example:

[example 1] To disable the Positive Limit of channel 0, set bit 1 to 1 (2#0001 converted to decimal is 10#1)

[example 2] To disable the Positive Limit of channel 1, set bit 5 to 1 (2#0001 0000 converted to decimal is 10#16)

Note: If the Home position is reused, the Homing function becomes invalid.

2. Host software IO Config Tool Demonstration

1. Procedure

After normal communication and configuration via the IO Config Tool software, enter the parameter setting screen shown below. The module's 16-bit digital input channel function configuration is displayed, with a default value of 0, which means the Positive/Negative Limit, Home position and Brake functions are used normally.

Detailed Configuration of Digital Inputs on Solidot's XB6S PTO Module

As shown in red box ①: the input channel icons of channels 0, 1 and 2 are default blank circles, indicating that the Positive/Negative Limit, Home position and Brake functions of these channels are in normal use.

As shown in black box ②: the four input channel icons of channel 3 are blue circles, indicating that the Positive/Negative Limit, Home position and Brake functions of this channel have been converted to standard DI inputs.

After selecting the channels to be configured, click the download button in box ③ to send the command to the module.

2. Result Demonstration

Detailed Configuration of Digital Inputs on Solidot's XB6S PTO Module

The Positive Limit input channels of channel 0 and channel 3 are both triggered. Channel 0 reports alarm code 4096 (Positive Limit alarm), while channel 3 does not trigger a limit alarm because its input channel function is set to standard DI input.

The above is a detailed explanation of the digital input function configuration of the Solidot remote I/O XB6S PTO pulse output module. Thank you for watching.