HomeKnowledgeHow to configure the XB6S-PN2002 with the XB6S-C01SP as a Modbus RTU master in TIA Portal

How to configure the XB6S-PN2002 with the XB6S-C01SP as a Modbus RTU master in TIA Portal

2026-06-14

Quick overview

 

1. Demo product

XB6S-PN2002+XB6S-C01SP

 

2. Configuration tool

Siemens TIA Portal

 

3. Communication mode

XB6S-C01SP configured as a Modbus RTU master, connected to a Siemens PLC via XB6S-PN2002

 

4. Demo slave

Encoder supporting the Modbus RTU protocol (read/write operations with function codes 03/06/10)

 

5. Operations involved

Serial port parameter configuration, control word setting, node parameter entry, I/O address read/write and communication status diagnostics

 

 

 

How can the Siemens PLC be connected to Modbus RTU slave devices and register read/write be implemented in TIA Portal via the Solidot slice PROFINET protocol Coupler XB6S-PN2002 combined with the serial Communication module XB6S-C01SP?

 

XB6S-PN2002 handles communication with the PLC on the PROFINET side, and XB6S-C01SP handles the Modbus RTU master function on the serial side. Together they allow all operations in TIA Portal: serial parameter configuration, node command entry, and I/O address read/write. This document uses an encoder supporting the Modbus RTU protocol as an example to demonstrate the complete configuration method for function codes 03/06/10.

 

 

1. Demo slave description

 

In this example, an encoder supporting the Modbus RTU protocol is used as the slave. The following three target register operations are found in its manual:

 

• function code 03: read 2 registers (read the encoder current value);

• function code 06: write a single register (reset zero point);

• function code 10: write 2 registers (set the current position).

Register Address

Description

Value range

Supported function
codes

Remarks

0 x 0000 ... 0 x 0001

Encoder value

.. 0xFFFFFFFF
(0 ... 4294967295)

0 x 03

 

 

0 x 0002

Encoder revolution count value

.. 0xFFFF
(0 ... 65535)

0 x 03

 

0 x 0003

Encoder single-turn value

.. 0xFFFF
(0 ... 65535)

0 x 03

 

0 x 0004

Encoder address

1-255

0 x 06

Communication address

0 x 0008

Encoder reset
Zero point flag bit

0 x 0001

0 x 06

Write 0 x 0001, the encoder uses
the current position as the zero point

0 x 0009

Encoder value
Increment direction

0 x 0000 ... 0 x 0001

0 x 06

0 x 00: Clockwise
0 x 01: Counterclockwise

0 x 000 A

Encoder angular velocity
Sampling time

.. 65535 (ms)

0 x 06

Default: 100 ms

0 x 000B ... 0 x 000C

Encoder setting
Current position value

.. 0xFFFFFFFF
(0 ... 4294967295)

0 x 10

Set the Encoder current position value

0 x 000E

Encoder setting
Midpoint flag

0 x 0001

0 x 06

Write 0 x 0001; the Encoder uses
the current position as the midpoint

0 x 000F

Encoder settings
5-turn flag bit

0 x 0001

0 x 06

Write 0 x 0001, the encoder uses
Current position as the 5-turn value

0 x 0020 ... 0 x 0021

Encoder angular velocity value

-2147483648 ... 2147483647

0 x 03

Signed integer

 

 

2. Configuring serial communication parameters in TIA Portal

 

In TIA Portal, select the XB6S-C01SP module, click "Properties" → "Module Parameters", and set the communication mode to "Modbus RTU master".

How to configure the XB6S-PN2002 with the XB6S-C01SP as a Modbus RTU master in TIA Portal

 

How to configure the XB6S-PN2002 with the XB6S-C01SP as a Modbus RTU master in TIA Portal

How to configure the XB6S-PN2002 with the XB6S-C01SP as a Modbus RTU master in TIA Portal

Set the baud rate, stop Bit, character format, and Parity mode according to the slave's serial parameters, and make sure the master and slave configurations match exactly.

 

Recommended control word parameters

If the control word is to be enabled, it is recommended to select "Level trigger" for the control mode, and set the response timeout to 200 ms and the Polling delay to 100 ms for greater communication stability.

How to configure the XB6S-PN2002 with the XB6S-C01SP as a Modbus RTU master in TIA Portal

 

Note: With default parameters, the Polling speed is relatively fast, and some slower-responding slave devices may not respond in time and report an error. Appropriately extending the response timeout and Polling delay can effectively improve communication stability.

 

Frame Interval parameter description

In general, leave the Frame Interval at the default 1.5T. If the serial debugging assistant communicates normally with the module and also with the slave device, but the module cannot communicate with the slave device, try gradually increasing the Frame Interval and testing.

 

 

3. Node parameter configuration

 

When the communication mode is Modbus RTU master and the control word has been enabled, fill in the parameters node by node according to the following rules. This example configures 3 commands, requiring nodes 1 to 4 in total:

Node

Parameter

Value to write

Corresponding command description

Node 1

Parameter 1

3 (3 nodes used in this example)

—

Node 1

Parameter 2

0 (default)

—

Node 2

Parameter 1

770 (0 x 00000302)

Function code 03, read 2 registers (encoder value), start address 0 x 0

Node 2

Parameter 2

1 (slave station number)

—

Node 3

Parameter 1

526079 (0 x 000806FF)

Function code 06, write single register (reset zero point), start address 0 x 8

Node 3

Parameter 2

1 (slave station number)

—

Node 4

Parameter 1

722434 (0 x 000B0602)

Function code 10, write 2 registers (set current position), start address 0xB

Node 4

Parameter 2

1 (slave station number)

—

 

How to configure the XB6S-PN2002 with the XB6S-C01SP as a Modbus RTU master in TIA Portal

Note: For node 1, parameter 1 is the number of Nodes actually used this time (3 in this example). From node 2 onward, each node corresponds to one Modbus command; parameter 1 is the decimal value converted from hexadecimal format, and parameter 2 is the slave Station number.

 

 

4. I/O address read/write and communication status diagnostics

 

After configuration is complete, control commands are sent via the Q addresses and status is read via the I addresses.

How to configure the XB6S-PN2002 with the XB6S-C01SP as a Modbus RTU master in TIA Portal

 

 

In this example, all addresses start at 0. The addresses are defined as follows:

6.3.1 Modbus master station process data

Upstream data (32 bytes)

byte number

Functions

Meaning

Address range

1 

status word

Bit0: Idle state

1 byte

Bit1: Busy state, i.e. data transmission in progress

Bit2: Completion state, i.e. data transmission complete

2 

alarm code

See alarm code

1 byte

3 

Input Data

Serial Communication module input data

the last 30 bytes

4 

Input Data

…

…

32 

Input Data

Downstream data (32 bytes)

byte number

Functions

Meaning

Address range

1 

control word

When the configuration parameter control mode is level, set to 1 to send data

1 byte

When the configuration parameter control mode is Rising Edge, 0- > 1 sends data

2 

Output Data

Serial Communication module output data

the last 31 bytes

3 

Output Data

…

...

32 

Output Data

Note: The process data in the table above is for 1 node configured in level or Rising Edge mode. If two nodes are configured, byte numbers 1
and 2 of the upstream data are the status bit and alarm code of node 1, byte numbers 3 and 4 are the status bit and alarm code of node 2, and the remaining bytes are data bits; byte
number 1 of the downstream data is the control bit of node 1, byte number 2 is the control bit of node 2, and the remaining bytes are data bits. Up to 15 nodes can be configured.

 

How to configure the XB6S-PN2002 with the XB6S-C01SP as a Modbus RTU master in TIA Portal

 

How to configure the XB6S-PN2002 with the XB6S-C01SP as a Modbus RTU master in TIA Portal

Node 2 participates in polling only when QB0=1. Likewise, to enable node 3 and node 4, QB1=1 and QB2=1 must be assigned.

 

During normal communication, status word BIT0/BIT1/BIT2 change; for example, the value of IB0 is typically seen alternating between 2 and 5, while the alarm code remains 0. If communication is abnormal, check the alarm code.

6.3.7 Modbus alarm code

fault code

Comment

0 x 00

No error

0 x 01

Slave device address error

0 x 02

Function code error

0 x 03

CRC check error

0 x 04

Response byte count error

0 x 05

Coil register data error

0 x 06

Holding register data error

0 x 07

Illegal data address

0 x 08

Slave device fault

0 x 09

LRC check error

0 x 0C

Data length error

0 x 0D

Data conversion error

0 x 0E

ASCII frame error

0 x 0F

Response timeout