After the Solidot remote I/O XB6S PROFINET protocol coupler XB6S-PN2002 has established communication successfully, if the IOE red LED flashes or the MT yellow LED is steady on, these are I/O-side alarms. This article explains troubleshooting and solutions in detail.

1. Load-side voltage Not Connected or Not Properly Connected
Output modules (XB6S-0032A, XB6S-0032B, XB6S-1616A, XB6S-1616B, XB6S-0012J/6, XB6S-A04V, XB6S-A08V, XB6S-A04I, XB6S-A08I) and some function modules (XB6S-PL20, XB6S-PL20D, XB6S-PT04A, XB6S-PS20D) all require a load-side power supply. If it is not connected, the module will generate an alarm.
If all connections are properly made, further troubleshooting is required. Use force output to check; if a module cannot output, check whether the wiring has poor contact or whether the voltage meets the requirement. Otherwise, the module will generate an alarm.
2. Analog value exceeding the measuring range
The analog inputs of the XB6S series all support the channel overflow/underflow function. If the value exceeds the current measuring range but not the maximum measuring range of the module, the current measuring range can be modified. If it exceeds the maximum measuring range of the module, check the sensor signal. (Exceeding the measuring range does not affect module operation.)
3. Temperature module triggering disconnection detection
When the temperature module receives no signal, the code value displays -9999 and disconnection detection is triggered. You can disable unused channels in the module properties, i.e., turn off the channels.

If disconnection detection is still triggered after the sensor is connected, check whether the sensor type is selected correctly. The default sensor type of the module is PT100. Select the correct type under sensor type selection in the properties.

4. Incorrect parameter configuration of the serial communication module
1. Incorrect node parameter configuration

As shown in the figure above, the node parameters do not conform to the module definition. Configure the correct node parameters according to the manual.
2. Parameter configuration exceeding the current byte count
2.1 disable mode

As shown in the figure above, the current node parameter configuration reads 16 registers each from slave 1 and slave 2, totaling 32 words (64 bytes), which exceeds the module's default 32 bytes for upstream and downstream data. You can manually change the module's byte count in the communication mode; a maximum of 255 bytes each for input and output is supported.

2.2 High-level trigger or rising edge trigger mode
When high-level trigger or rising edge trigger mode is configured, the upstream data allocates a two-byte status word and alarm code to each node.
Upstream data (32 bytes) | |||
byte number | Functions | Meaning | Address range |
1 | status word | Bit0: Idle state | 1 byte |
Bit1: Busy state, i.e., data is being transmitted. | |||
Bit2: Complete state, i.e., data transmission is complete. | |||
2 | alarm code | See alarm code | 1 byte |
3 | Input Data | Serial Communication module input data | Last 30 bytes |
4 | Input Data | ||
… | … | ||
32 | Input Data | ||
Downstream data (32 bytes) | |||
byte number | Functions | Meaning | Address range |
1 | control word | When the configuration parameter control mode is level, set to 1 to send data | 1 byte |
When the configuration parameter control mode is Rising Edge, 0- > 1 sends data | |||
2 | Output Data | Serial Communication module output data | the last 31 bytes |
3 | Output Data | ||
... | ... | ||
32 | Output Data | ||
Note: The process data in the table above is Level or Rising Edge mode when 1 node is configured. If two nodes are configured, byte numbers 1 | |||

As shown in the figure above, only device 1 is read with 16 registers, 32 bytes, which does not exceed the module's default 32 bytes of upstream data. However, level trigger is configured, and the status word and alarm code in the upstream data occupy two bytes, resulting in a total input data of 34 bytes, which exceeds the module's data receiving area. You can manually change the module's byte count or change parameter 1 of node 2 to 783 to read 15 registers, making the total input data 32 bytes.
The above is the I/O-side alarm troubleshooting and solutions for the Solidot remote I/O XB6S PROFINET protocol coupler. Thank you for watching!