HomeKnowledgeSolidot remote I/O XB6S PROFINET protocol Coupler I/O-side alarm Troubleshooting and Solutions

Solidot remote I/O XB6S PROFINET protocol Coupler I/O-side alarm Troubleshooting and Solutions

2025-08-10

After the Solidot remote I/O XB6S PROFINET protocol coupler XB6S-PN2002 has established communication successfully, if the IOE red LED flashes or the MT yellow LED is steady on, these are I/O-side alarms. This article explains troubleshooting and solutions in detail.

Solidot remote I/O XB6S PROFINET protocol Coupler I/O-side alarm Troubleshooting and Solutions

 

 

1. Load-side voltage Not Connected or Not Properly Connected

Output modules (XB6S-0032A, XB6S-0032B, XB6S-1616A, XB6S-1616B, XB6S-0012J/6, XB6S-A04V, XB6S-A08V, XB6S-A04I, XB6S-A08I) and some function modules (XB6S-PL20, XB6S-PL20D, XB6S-PT04A, XB6S-PS20D) all require a load-side power supply. If it is not connected, the module will generate an alarm.

 

If all connections are properly made, further troubleshooting is required. Use force output to check; if a module cannot output, check whether the wiring has poor contact or whether the voltage meets the requirement. Otherwise, the module will generate an alarm.

 

2. Analog value exceeding the measuring range

The analog inputs of the XB6S series all support the channel overflow/underflow function. If the value exceeds the current measuring range but not the maximum measuring range of the module, the current measuring range can be modified. If it exceeds the maximum measuring range of the module, check the sensor signal. (Exceeding the measuring range does not affect module operation.)

 

3. Temperature module triggering disconnection detection

When the temperature module receives no signal, the code value displays -9999 and disconnection detection is triggered. You can disable unused channels in the module properties, i.e., turn off the channels.

Solidot remote I/O XB6S PROFINET protocol Coupler I/O-side alarm Troubleshooting and Solutions

 

If disconnection detection is still triggered after the sensor is connected, check whether the sensor type is selected correctly. The default sensor type of the module is PT100. Select the correct type under sensor type selection in the properties.

Solidot remote I/O XB6S PROFINET protocol Coupler I/O-side alarm Troubleshooting and Solutions

 

 

4. Incorrect parameter configuration of the serial communication module

1. Incorrect node parameter configuration

Solidot remote I/O XB6S PROFINET protocol Coupler I/O-side alarm Troubleshooting and Solutions

 

As shown in the figure above, the node parameters do not conform to the module definition. Configure the correct node parameters according to the manual.

2. Parameter configuration exceeding the current byte count

2.1 disable mode

Solidot remote I/O XB6S PROFINET protocol Coupler I/O-side alarm Troubleshooting and Solutions

 

As shown in the figure above, the current node parameter configuration reads 16 registers each from slave 1 and slave 2, totaling 32 words (64 bytes), which exceeds the module's default 32 bytes for upstream and downstream data. You can manually change the module's byte count in the communication mode; a maximum of 255 bytes each for input and output is supported.

Solidot remote I/O XB6S PROFINET protocol Coupler I/O-side alarm Troubleshooting and Solutions

 

2.2 High-level trigger or rising edge trigger mode

When high-level trigger or rising edge trigger mode is configured, the upstream data allocates a two-byte status word and alarm code to each node.

Upstream data (32 bytes)

byte number

Functions

Meaning

Address range

1 

status word

Bit0: Idle state

1 byte

Bit1: Busy state, i.e., data is being transmitted.

Bit2: Complete state, i.e., data transmission is complete.

2 

alarm code

See alarm code

1 byte

3 

Input Data

Serial Communication module input data

Last 30 bytes

4 

Input Data

…

…

32 

Input Data

Downstream data (32 bytes)

byte number

Functions

Meaning

Address range

1 

control word

When the configuration parameter control mode is level, set to 1 to send data

1 byte

When the configuration parameter control mode is Rising Edge, 0- > 1 sends data

2 

Output Data

Serial Communication module output data

the last 31 bytes

3 

Output Data

...

...

32 

Output Data

  Note: The process data in the table above is Level or Rising Edge mode when 1 node is configured. If two nodes are configured, byte numbers 1
and 2 of the upstream data are the status bit and alarm code of node 1, byte numbers 3 and 4 are the status bit and alarm code of node 2, and the remaining bytes are data bits; byte
number 1 of the downstream data is the control bit of node 1, byte number 2 is the control bit of node 2, and the remaining bytes are data bits. Up to 15 nodes can be configured.

 

Solidot remote I/O XB6S PROFINET protocol Coupler I/O-side alarm Troubleshooting and Solutions

As shown in the figure above, only device 1 is read with 16 registers, 32 bytes, which does not exceed the module's default 32 bytes of upstream data. However, level trigger is configured, and the status word and alarm code in the upstream data occupy two bytes, resulting in a total input data of 34 bytes, which exceeds the module's data receiving area. You can manually change the module's byte count or change parameter 1 of node 2 to 783 to read 15 registers, making the total input data 32 bytes.

 

 

The above is the I/O-side alarm troubleshooting and solutions for the Solidot remote I/O XB6S PROFINET protocol coupler. Thank you for watching!