↑ Solidot EtherNet/IP Coupler KitXB6-EI2002ST
1. digital I/O modules under the EtherNet/IP protocol
Each module is allocated a 4-byte data unit; each channel occupies 1 bit. The actual data length used varies with the number of channels on the module.
2. Analog I/O modules under the EtherNet/IP protocol
Each module is allocated a 16-byte data unit. Each channel occupies 2 bytes. The actual data length used varies with the number of channels on the module.
The data length allocation is shown in the following table:
Module Model | Upstream process data length (bytes) | Downstream process data length (bytes) | ||
Assigned value | Actual value used | Assigned value | Actual value used | |
XB6-EI0002ST | 4 | 4 | - | - |
XB6-3200A/B | 4 | 4 | - | - |
XB6-1600A/B | 4 | 2 | - | - |
XB6-0800A/B | 4 | 1 | - | - |
XB6-0032A/B | - | - | 4 | 4 |
XB6-0016A/B | - | - | 4 | 2 |
XB6-0008A/B | - | - | 4 | 1 |
XB6-1616A/B | 4 | 2 | 4 | 2 |
- | - | 4 | 2 | |
XB6-VT16 | - | - | 4 | 2 |
16 | 16 | - | - | |
16 | 8 | - | - | |
16 | 16 | - | - | |
16 | 8 | - | - | |
- | - | 16 | 16 | |
- | - | 16 | 8 | |
- | - | 16 | 16 | |
- | - | 16 | 8 | |
16 | 16 | 16 | 16 | |
16 | 8 | 16 | 8 | |
20 | 20 | 16 | 12 | |
20 | 20 | 2 | 2 | |
24 | 24 | 36 | 36 | |
40 | 40 | 40 | 40 | |
note: The upstream and downstream byte lengths are calculated based on the allocated values. If the allocated value for a module is greater than the actual value, the excess byte addresses are reserved and have no practical meaning. For example, the XB6-1600A requires 4 upstream bytes to be allocated, but the actual 16 points occupy 2 upstream bytes, so the excess 2 upstream bytes are reserved.
The coupler is allocated 4 bytes of data, used for coupler status indication and alarms, and for defining the backplane bus status indication and topology comparison prompts. The coupler occupies the first 4 bytes of the upstream (input) addresses. The communication normal status feedback word is 4 and 0.
Backplane bus status indication:
Status value | Status definition | Description |
1 | Backplane bus initialization | Backplane bus initialization phase |
2 | Backplane bus ready state | Backplane bus pre-connected; only parameter download is performed |
4 | Backplane bus enabled state | Backplane bus connection enabled; process data exchange is performed |
Topology status comparison indication:
Status value | Explanation |
0 | Topology comparison OK |
1 | An I/O module type mismatch exists in the topology |
2 | No topology configured |
3 | A missing I/O module exists in the topology |
4 | An excess I/O module exists in the topology |
5 | An I/O module type not supported by the coupler exists in the topology |
example:
1. Taking a KEYENCE master as an example, configure and calculate the upstream (input) and downstream (output) byte lengths of the modules as follows:
XB6-P2000H (the power supply module does not occupy input/output length) |
XB6-EI0002ST(occupies 4 bytes of input) |
XB6-3200A(occupies 4 bytes of input) |
XB6-1600A(occupies 4 bytes of input) |
XB6-0016A(occupies 4 bytes of output) |
XB6-0032B(occupies 4 bytes of output) |
XB6-A40I(occupies 16 bytes of input) |
XB6-A08V(occupies 16 bytes of output) |
XB6-A40TM(occupies 16 bytes of input and 16 bytes of output) |
XB6-C01SP(occupies 40 bytes of input and 40 bytes of output) |
XB6-CVR00(the End cover does not occupy input or output length; it must be fitted and pressed firmly in place during actual use) |
In summary, the calculated upstream byte length is 84, and the downstream byte length is 80.

2. Configure the I/O modules; the model and position must match the actual hardware:

3. Upstream address assignment:

4. Downstream address assignment:

note: The low 8 bits of W036 are the compensation temperature for XB6-A40TM channel 1, and the high 8 bits are the compensation temperature for XB6-A40TM channel 2; the low 8 bits of W037 are the compensation temperature for XB6-A40TM channel 3, and the high 8 bits are the compensation temperature for XB6-A40TM channel 4.